Underground Storage Tank Leak Detection
|
MassTech is not one test technology but a suite of more than a dozen, each with its own application and strength. Each technology is third party certified to US EPA, most to better than 0.38 lt/hr. The most important are NWG (US EPA) listed, an honour not normally accorded to non-USA methods. The latest certifications are for volumetric high precision tests and are among the most accurate and sensitive in the world. To test a tank and line system fully requires more than one technology and the normal MassTech protocols run these tests concurrently. The technician on site makes a decision on the most useful test strategy by comparing the client’s requirement for the test, the client’s operational needs and the situation on the site. Where either of the operational needs and the situation on site conflict with the needs of the test, the client needs to be guided but ultimately will make the decision on test strategy having been advised of the implications. |
![]() |
|
Motives for Testing |
||
|
Tanks are tested to confirm their health or to explain and diagnose problems. In the case of confirming health, tests are normally conducted: prior to commissioning, on change of responsibility or on particular birthdays of either the tank or of the installation or of the site licence. MassTech uses a protocol called Pascal Perfect for the first two of these requirements so that installation or maintenance faults are picked up before the owner takes on the onerous responsibility of running the site. Where tests are used to diagnose faults, the type of suspected fault should guide the test protocol. Faults may be suspected in the face of the following evidence:
Situations which can cause problems for tank testers |
![]() |
|
|
![]() |
|
The Ideal Test |
||
|
For the tank itself, the test protocol which provides the most secure result is as follows: The tank is free vented for long enough that the ullage pressure is at barometric. Two or three sets of mass readings sandwiched between atmospheric readings are taken. The tank is sealed and pressure recorded every 10 seconds for 25 minutes. The tank is free vented again for long enough that the ullage pressure is at barometric. Two or three sets of mass readings sandwiched between atmospheric readings are taken. The tank is sealed, pressurised with nitrogen to 10 kPa above barometric pressure and the pressure recorded every 10 seconds for between 25 minutes and 2 hours according to ullage volume. The tank is free vented again for long enough that the ullage pressure is at barometric. Two or three sets of mass readings sandwiched between atmospheric readings are taken. There are circumstances where parts of this test can be shortened or even excluded but these are rare and exclusions could render the test inconclusive. Situations which may result in an Inconclusive Result
Situations which may result in an Incorrect ResultThere has never been an incorrect result called in MassTech’s twelve years in tank testing confirming the closeness of MassTech’s EPA probability of detection (P(D)) to 100%. However unlikely or inconvenient a result may seem, it is independent, analysed by specialist experts and is valid. |
![]() |
|